ABB RET670 Applications Manual page 648

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
642
Section 1
(WA1)A1
(WA2)B1
(WA7)C
BB_ES
ABC_LINE
ANSI04000505 V1 EN
Figure 266:
Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BB_DC_OP
All disconnectors on this part of the busbar are open.
VP_BB_DC
The switch status of all disconnector on this part of the busbar is valid.
EXDU_BB
No transmission error from any bay containing the above information.
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),
and each bus-coupler bay (ABC_BC) are needed:
Signal
189OPTR
189 is open.
289OPTR
289 is open (AB_TRAFO, ABC_LINE)
22089OTR
289 and 2089 are open (ABC_BC)
789OPTR
789 is open.
VP189TR
The switch status of 189 is valid.
VP289TR
The switch status of 289 is valid.
V22089TR
The switch status of 289and 2089 is valid.
VP789TR
The switch status of 789 is valid.
EXDU_BB
No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed.
For B1B2_DC, corresponding signals from busbar B are used. The same type of
module (A1A2_DC) is used for different busbars, that is, for both bus-section
disconnectors A1A2_DC and B1B2_DC.
Signal
DCOPTR
The bus-section disconnector is open.
VPDCTR
The switch status of bus-section disconnector DC is valid.
EXDU_DC
No transmission error from the bay that contains the above information.
A1A2_DC(BS)
B1B2_DC(BS)
ABC_BC
AB_TRAFO
1MRK504116-UUS C
Section 2
A2
B2
C
BB_ES
ABC_LINE
en04000505_ansi.vsd
Application manual