Setting Parameters - ABB RET670 Applications Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK504116-UUS C
3.15.1.4
Table 215:
CVMMXN Non group settings (basic)
Name
Values (Range)
SLowLim
0.0 - 2000.0
SLowLowLim
0.0 - 2000.0
SMin
0.0 - 2000.0
SMax
0.0 - 2000.0
SRepTyp
Cyclic
Dead band
Int deadband
PMin
-2000.0 - 2000.0
PMax
-2000.0 - 2000.0
PRepTyp
Cyclic
Dead band
Int deadband
QMin
-2000.0 - 2000.0
QMax
-2000.0 - 2000.0
Table continues on next page
Application manual
Table 214:
General settings parameters for the Measurement function
Setting
Short description
Operation
Operation Off/On
PowAmpFact
Amplitude factor to scale power
calculations
PowAngComp
Angle compensation for phase
shift between measured I & V
Mode
Selection of measured current
and voltage
k
Low pass filter coefficient for
power measurement, V and I
VGenZeroDb
Zero point clamping in % of
Vbase
IGenZeroDb
Zero point clamping in % of Ibase
VBase
Base setting for voltage level in
kV
IBase
Base setting for current level in A

Setting parameters

The available setting parameters of the measurement function (MMXU, MSQI) are
depending on the actual hardware (TRM) and the logic configuration made in PCM600.
Unit
Step
%SB
0.1
%SB
0.1
%SB
0.1
%SB
0.1
-
-
%SB
0.1
%SB
0.1
-
-
%SB
0.1
%SB
0.1
Selected
Comment
value
On
1.000
0.0
Arone
0.00
25%
3
15,65
3690
Default
Description
80.0
Low limit in % of SBase
60.0
Low Low limit in % of SBase
50.0
Minimum value in % of SBase
200.0
Maximum value in % of SBase
Cyclic
Reporting type
-200.0
Minimum value in % of SBase
200.0
Maximum value in % of SBase
Cyclic
Reporting type
-200.0
Minimum value in % of SBase
200.0
Maximum value in % of SBase
Section 3
IED application
On
Function must be
Typically no scaling is required
Typically no angle compensation is
required. As well here required
direction of P & Q measurement is
towards protected object (as per IED
internal default direction)
Generator VTs are connected
between phases (V-connected)
Typically no additional filtering is
required
Set minimum voltage level to 25%
Set minimum current level to 3%
Set generator rated phase-to-phase
voltage
Set generator rated current
761