Section 3
IED application
3.12.3.9
650
989_OP = VOLT_OFF
989_CL = VOLT_ON
If there is no voltage supervision, then set the corresponding inputs as follows:
VOLT_OFF = 1
VOLT_ON = 0

Interlocking for breaker-and-a-half diameter BH (3)

Application
The interlocking for breaker-and-a-half diameter (BH_CONN(3), BH_LINE_A(3),
BH_LINE_B(3)) functions are used for lines connected to a breaker-and-a-half
diameter according to figure 275.
189
152
689
BH_LINE_A
989
989G
ANSI04000513 V1 EN
Figure 275:
Switchyard layout breaker-and-a-half
Three types of interlocking modules per diameter are defined. BH_LINE_A (3) and
BH_LINE_B (3) are the connections from a line to a busbar. BH_CONN (3) is the
189G
289G
389G
6189
6289
152
289G
189G
BH_CONN
1MRK504116-UUS C
WA1 (A)
WA2 (B)
289
189G
152
289G
689
389G
BH_LINE_B
989
989G
en04000513_ansi.vsd