ABB RET670 Applications Manual page 250

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
244
Check the reduction of a reach for the overreaching zones due to the effect of the zero
sequence mutual coupling. The reach is reduced for a factor:
Z
0
m
= -
K
0 1
×
+
+
2
Z
1
Z
0
R
f
EQUATION1426 V1 EN
If the denominator in equation
real and imaginary part of the reach reduction factor for the overreaching zones can be
written as:
×
X m
0
Re
( )
= -
Re
K
0
1
( )
2
+
Re
B
Im
EQUATION1427 V2 EN
( )
×
X m
0
Im
( )
=
Im
K
0
( )
2
+
Re
B
Im
EQUATION1428 V2 EN
Parallel line is out of service and grounded in both ends
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit for
the single phase-to-ground-faults. Set the values of the corresponding zone (zero-
sequence resistance and reactance) equal to:
2
æ
X
m0
×
ç
------------------------- -
R
=
R
1
+
0E
0
2
2
è
R
X
+
0
0
EQUATION561 V1 EN
2
æ
X
m0
×
X
=
X
ç
1
------------------------- -
0E
0
2
2
è
R
X
+
0
0
EQUATION562 V1 EN
Setting of reach in resistive direction
Set the resistive reach independently for each zone, and separately for phase-to-phase
(R1PP), and phase-to-ground loop (R1PG) measurement.
Set separately the expected fault resistance for phase-to-phase faults (R1PP) and for
the phase-to-ground faults (RFPG) for each zone. Set all remaining reach setting
parameters independently of each other for each distance zone.
155
is called B and Z0m is simplified to X0m, then the
( )
B
( )
2
B
B
( )
2
B
ö
÷
ø
ö
÷
ø
1MRK504116-UUS C
(Equation 155)
(Equation 156)
(Equation 157)
(Equation 158)
(Equation 159)
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents