1MRK504116-UUS C
3.8.4.3
Table 132:
OEXPVPH (24) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
VBase
0.05 - 2000.00
Pickup1
100.0 - 180.0
Pickup2
100.0 - 200.0
XLeakage
0.000 - 200.000
t_TripPulse
0.000 - 60.000
t_MinTripDelay
0.000 - 60.000
Table continues on next page
Application manual
V/Hz
%
150
140
130
120
110
100
0.05
0.1
0.2
0.5
t6
t5
t4
IEC01000377 V1 EN
Figure 218:
Example on overexcitation capability curve and V/Hz protection
settings for power transformer

Setting parameters

Unit
Step
-
-
A
1
kV
0.05
%VB/f
0.1
%VB/f
0.1
ohm
0.001
s
0.001
s
0.001
transformer capability curve
relay operate characteristic
1
2
5
10
t3
t2
Default
Description
Disabled
Disable/Enable Operation
3000
Base current (rated phase current) in A
400.00
Base voltage (main voltage) in kV
110.0
Operate level of V/Hz at no load and rated
freq in % of (Vbase/frated)
140.0
High level of V/Hz above which tMin is used,
in % of (Vbase/fn)
0.000
Winding leakage reactance in primary ohms
0.100
Length of the pulse for trip signal (in sec)
7.000
Minimum trip delay for V/Hz inverse curve, in
sec
Section 3
IED application
Continous
20
50
100
200
(minutes)
t1
en01000377.vsd
Time
535