Setting Parameters - ABB RET670 Applications Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK504116-UUS C
3.7.6.3
Table 100:
SDEPSDE (67N) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OpModeSel
3I0Cosfi
3I03V0Cosfi
3I0 and fi
DirMode
Forward
Reverse
RCADir
-179 - 180
RCAComp
-10.0 - 10.0
ROADir
0 - 90
INCosPhiPU
0.25 - 200.00
SN_PU
0.25 - 200.00
INDirPU
0.25 - 200.00
tDef
0.000 - 60.000
SRef
0.03 - 200.00
TDSN
0.00 - 2.00
OpINNonDir
Disabled
Enabled
INNonDirPU
1.00 - 400.00
tINNonDir
0.000 - 60.000
Table continues on next page
Application manual

Setting parameters

Unit
Step
-
-
-
-
-
-
Deg
1
Deg
0.1
Deg
1
%IB
0.01
%SB
0.01
%IB
0.01
s
0.001
%SB
0.01
-
0.01
-
-
%IB
0.01
s
0.001
Default
Description
Disabled
Operation Disable / Enable
3I0Cosfi
Selection of operation mode for protection
Forward
Direction of operation forward or reverse
-90
Relay characteristic angle RCA, in deg
0.0
Relay characteristic angle compensation
90
Relay open angle ROA used as release in
phase mode, in deg
1.00
Set level for 3I0cosFi, directional res over
current, in %Ib
10.00
Set level for 3I03V0cosFi, pickup inv time
count, in %Sb
5.00
Set level for directional residual over current
prot, in %Ib
0.100
Definite time delay directional residual
overcurrent, in sec
10.00
Reference value of res power for inverse time
count, in %Sb
0.10
Time multiplier setting for directional residual
power mode
Disabled
Operation of non-directional residual
overcurrent protection
10.00
Set level for non directional residual over
current, in %Ib
1.000
Time delay for non-directional residual over
current, in sec
Section 3
IED application
463

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents