ABB RET670 Applications Manual page 764

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
758
132kV Busbar
200/5
31.5 MVA
P
500/5
33kV Busbar
ANSI09000040 V1 EN
Figure 307:
Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure 307, it is
necessary to do the following:
1.
Set correctly all CT and VT and phase angle reference channel PhaseAngleRef
(see section
"Analog
2.
Connect, in PCM600, measurement function to LV side CT & VT inputs
3.
Set the setting parameters for relevant Measurement function as shown in the
following table 213:
IED
Q
V
AB
33kV 120V
/
3
3
ANSI09000040-1-en.vsd
inputs") data using PCM600 for analog input channels
1MRK504116-UUS C
Application manual