ABB RET670 Applications Manual page 797

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK504116-UUS C
Table 231:
A4RADR Non group settings (basic)
Name
Values (Range)
Operation31
Disabled
Enabled
NomValue31
0.0 - 999999.9
UnderTrigOp31
Disabled
Enabled
UnderTrigLe31
0 - 200
OverTrigOp31
Disabled
Enabled
OverTrigLe31
0 - 5000
Operation32
Disabled
Enabled
NomValue32
0.0 - 999999.9
UnderTrigOp32
Disabled
Enabled
UnderTrigLe32
0 - 200
OverTrigOp32
Disabled
Enabled
OverTrigLe32
0 - 5000
Operation33
Disabled
Enabled
NomValue33
0.0 - 999999.9
UnderTrigOp33
Disabled
Enabled
UnderTrigLe33
0 - 200
OverTrigOp33
Disabled
Enabled
OverTrigLe33
0 - 5000
Operation34
Disabled
Enabled
NomValue34
0.0 - 999999.9
UnderTrigOp34
Disabled
Enabled
UnderTrigLe34
0 - 200
OverTrigOp34
Disabled
Enabled
Table continues on next page
Application manual
Unit
Step
Default
-
-
Disabled
-
0.1
0.0
-
-
Disabled
%
1
50
-
-
Disabled
%
1
200
-
-
Disabled
-
0.1
0.0
-
-
Disabled
%
1
50
-
-
Disabled
%
1
200
-
-
Disabled
-
0.1
0.0
-
-
Disabled
%
1
50
-
-
Disabled
%
1
200
-
-
Disabled
-
0.1
0.0
-
-
Disabled
%
1
50
-
-
Disabled
IED application
Description
Operation On/off
Nominal value for analog channel 31
Use under level trig for analog cha 31 (on) or
not (off)
Under trigger level for analog cha 31 in % of
signal
Use over level trig for analog cha 31 (on) or
not (off)
Over trigger level for analog cha 31 in % of
signal
Operation On/off
Nominal value for analog channel 32
Use under level trig for analog cha 32 (on) or
not (off)
Under trigger level for analog cha 32 in % of
signal
Use over level trig for analog cha 32 (on) or
not (off)
Over trigger level for analog cha 32 in % of
signal
Operation On/off
Nominal value for analog channel 33
Use under level trig for analog cha 33 (on) or
not (off)
Under trigger level for analog cha 33 in % of
signal
Use over level trig for analog cha 33 (on) or
not (off)
Overtrigger level for analog cha 33 in % of
signal
Operation On/off
Nominal value for analog channel 34
Use under level trig for analog cha 34 (on) or
not (off)
Under trigger level for analog cha 34 in % of
signal
Use over level trig for analog cha 34 (on) or
not (off)
Section 3
791

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents