Setting Parameters - ABB RET670 Applications Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 3
IED application
3.7.14.3
Table 122:
NS2PTOC (46I2) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
tAlarm
0.00 - 6000.00
OpStep1
Disabled
Enabled
I2-1>
3 - 500
CurveType1
Definite
Inverse
t1
0.00 - 6000.00
tResetDef1
0.000 - 60.000
K1
1.0 - 99.0
t1Min
0.000 - 60.000
t1Max
0.00 - 6000.00
ResetMultip1
0.01 - 20.00
OpStep2
Disabled
Enabled
I2-2>
3 - 500
CurveType2
Definite
Inverse
t2
0.00 - 6000.00
tResetDef2
0.000 - 60.000
K2
1.0 - 99.0
t2Min
0.000 - 60.000
t2Max
0.00 - 6000.00
ResetMultip2
0.01 - 20.00
508

Setting parameters

Unit
Step
-
-
A
1
s
0.01
-
-
%IB
1
-
-
s
0.01
s
0.001
s
0.1
s
0.001
s
0.01
-
0.01
-
-
%IB
1
-
-
s
0.01
s
0.001
s
0.1
s
0.001
s
0.01
-
0.01
Default
Description
Disabled
Disable/Enable Operation
3000
Rated generator current in primary amps
3.00
Time delay for alarm ( operated by pick up
signal) in seconds
Enabled
Enable execution of step 1
10
Step 1 Neg. Seq. Current pickup level, in %
of IBase
Definite
Selection of definite or inverse time-
characteri. for step 1
10.00
Definite time delay for trip of step 1, in sec
0.000
Time delay for reset of definite timer of step 1,
in sec
10.0
Neg. seq. capability value of generator for
step 1, in sec
5.000
Minimum trip time for inverse delay of step 1,
in sec
1000.00
Maximum trip delay for step 1, in sec
1.00
Reset multiplier for K1, defines reset time of
inverse curve
Enabled
Enable execution of step 2
10
Step 2 Neg. Seq. Current pickup level, in %
of IBase
Definite
Selection of definite or inverse time-
characteri. for step 2
10.00
Definite time delay for trip of step 2, in sec
0.000
Time delay for reset of definite timer of step 2,
in sec
10.0
Neg. seq. capability value of generator for
step 2, in sec
5.000
Minimum trip time for inverse delay of step 2,
in sec
1000.00
Maximum trip delay for step 2, in sec
1.00
Reset multiplier for K2, defines reset time of
inverse curve
1MRK504116-UUS C
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents