Section 4
Station communication
4.7.1
4.7.2
4.7.2.1
4.7.3
Table 261:
MULTICMDRCV Non group settings (basic)
Name
Values (Range)
tMaxCycleTime
0.050 - 200.000
tMinCycleTime
0.000 - 200.000
Mode
Steady
Pulsed
tPulseTime
0.000 - 60.000
Table 262:
MULTICMDSND Non group settings (basic)
Name
Values (Range)
tMaxCycleTime
0.000 - 200.000
tMinCycleTime
0.000 - 200.000
844

Application

The IED can be provided with a function to send and receive signals to and from other
IEDs via the interbay bus. The send and receive function blocks has 16 outputs/inputs
that can be used, together with the configuration logic circuits, for control purposes
within the IED or via binary outputs. When it is used to communicate with other IEDs,
these IEDs have a corresponding Multiple transmit function block with 16 outputs to
send the information received by the command block.
Setting guidelines
Settings
The parameters for the multiple command function are set via PCM600.
The Mode setting sets the outputs to either a Steady or Pulsed mode.
Setting parameters
Unit
Step
s
0.001
s
0.001
-
-
s
0.001
Unit
Step
s
0.001
s
0.001
Default
Description
11.000
Maximum cycle time between receptions of
input data
0.000
Minimum cycle time between receptions of
input data
Steady
Mode for output signals
0.200
Pulse length for multi command outputs
Default
Description
5.000
Maximum time interval between transmission
of output data
0.000
Minimum time interval between transmission
of output data
1MRK504116-UUS C
Application manual