Configuration Guidelines - ABB RELION 670 SERIES Applications Manual

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

Section 15
Control
15.4.1
15.4.2
700
The positions of all switching devices in a bay and from some other bays determine the
conditions for operational interlocking. Conditions from other stations are usually not
available. Therefore, a line grounding switch is usually not fully interlocked. The operator
must be convinced that the line is not energized from the other side before closing the
grounding switch. As an option, a voltage indication can be used for interlocking. Take
care to avoid a dangerous enable condition at the loss of a VT secondary voltage, for
example, because of a blown fuse.
The switch positions used by the operational interlocking logic are obtained from
auxiliary contacts or position sensors. For each end position (open or closed) a true
indication is needed - thus forming a double indication. The apparatus control function
continuously checks its consistency. If neither condition is high (1 or TRUE), the switch
may be in an intermediate position, for example, moving. This dynamic state may
continue for some time, which in the case of disconnectors may be up to 10 seconds.
Should both indications stay low for a longer period, the position indication will be
interpreted as unknown. If both indications stay high, something is wrong, and the state is
again treated as unknown.
In both cases an alarm is sent to the operator. Indications from position sensors shall be
self-checked and system faults indicated by a fault signal. In the interlocking logic, the
signals are used to avoid dangerous enable or release conditions. When the switching state
of a switching device cannot be determined operation is not permitted.
For switches with an individual operation gear per phase, the evaluation must consider
possible phase discrepancies. This is done with the aid of an AND-function for all three
phases in each apparatus for both open and close indications. Phase discrepancies will
result in an unknown double indication state.

Configuration guidelines

The following sections describe how the interlocking for a certain switchgear
configuration can be realized in the IED by using standard interlocking modules and their
interconnections. They also describe the configuration settings. The inputs for delivery
specific conditions (Qx_EXy) are set to 1=TRUE if they are not used, except in the
following cases:
989_EX2 and 989_EX4 in modules BH_LINE_A and BH_LINE_B
152_EX3 in module AB_TRAFO
when they are set to 0=FALSE.
Interlocking for line bay ABC_LINE (3)
1MRK 506 369-UUS -
Line distance protection REL670 2.2 ANSI
Application manual