Accept the settings by clicking OK.
The function modules are also correspondingly set in the SINAMICS DCP by connecting
online and downloading.
7.4.2

Activating online via parameters

Note
This process is not supported by STARTER because it uses its own mechanisms.
Activation is through p0108. r0108 and is available at each DO as a display parameter for
the activated function modules.
The setting is made on p0108[i] in the Control Unit. In this case, the index corresponds to the
DO.
Index 0 stands for the CU,
Index 1 for the first DO – the default is the closed loop control DO DC_CTRL,
Index 2 optionally the first TMxx, etc.
SINAMICS DCP
Operating Instructions, 05/2016, A5E34382853K
Selecting the function modules
Commissioning
7.4 Activating function modules
103