Operation
8.1 Operation
Note
During a data save operation initiated by the user, the electronics power supply for the
SINAMICS DCP must not be interrupted.
An active data save operation is indicated by the following actions:
• The RDY LED flashes (see Chapter Description of the LEDs on the CUD (Page 247))
• The BOP20 flashes
Interrupting the electronics power supply while saving can lead to the loss of the current
device parameter assignment. See also Chapter Memory card functions (Page 113).
Drive object (DC_CTRL)
● p0010 Commissioning parameter filter
8.1.2.2

Display and operation with the BOP20

Characteristics
● Status display
● Changing the active drive object
● Displaying/changing parameters
● Displaying/acknowledging faults and alarms
● SINAMICS DCP controlled by the BOP20
Status display
The status display for each drive object can be set using p0005 and p0006.
Using the status display, you can switch to the parameter display or to a different drive
object. The following functions are supported:
● Changing the active drive object
– Press the "FN" and "Arrow up" keys -> the drive object number at the top left flashes
– Select the required drive object using the arrow keys
– Confirm with the "P" key
● Parameter display
– Press the "P" key
– The required parameter can be selected using the arrow keys
– Press the "FN" key -> parameter r0000 is displayed
– Press the "P" key -> returns to the status display
126
Operating Instructions, 05/2016, A5E34382853K
SINAMICS DCP