Siemens sinamics dcp Operating Instructions Manual page 51

Dc/dc power converter
Hide thumbs Also See for sinamics dcp:
Table of Contents

Advertisement

9
HLSA1
10
HLSA2
Terminal type: Spring-loaded terminal
● Type: PELV 24 V circuit
● Voltage tolerance of the P24 V ext: 18 V to 30 V for 30 kW devices, In = 5 A
● Conductor cross-sections: 1.5 to 2.5 mm
For 120 kW devices, for connections P24 V ext and M ext, a cross-section of 2.5 mm2
must be used.
Contact rating of the "NO contact for the contactor control": 2 A at 30 VAC/DC resistive.
Communication connections
The cables for PROFIBUS or PROFINET must be connected inside the device. The front
cover must be removed for this.
● The PROFIBUS connector X126 is on the CUD module. The cable can be led out at the
bottom through the intended aperture.
● The PROFINET connector X1400 is on the CBE20 module. The cable can be brought out
at the top through the opening provided for this purpose.
Image 6-10
SINAMICS DCP
Operating Instructions, 05/2016, A5E34382853K
NO contact for contactor control:
NO contact for contactor control:
for 120 kW devices, In = 20 A
PROFIBUS cable
PROFIBUS connection for the 30 kW device or 120 kW device
6.4 Terminals and connectors
Line contactor output
Line contactor output
2.
Electrical connection
51