8.4.3.3

Description of the status word

Table 8- 16
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
SINAMICS DCP
Operating Instructions, 05/2016, A5E34382853K
Description of status word 1 (ZSW1)
Meaning
Ready for switching on
Ready for operation
Operation enabled
reserved
No OFF2 active
No OFF3 active
Switching on inhibited
active
Device ready
Controller enable
Control request
"1" is always present
reserved
Pulses enabled
reserved
reserved
reserved
8.4 Communication according to PROFIdrive
Explanation
1
Ready for switching on
Power supply on, electronics initialized, line
contactors are open, pulses inhibited
0
Not ready for switching on
1
Ready for operation
Line contactors are closed.
0
Not ready for operation
Reason: No ON command has been issued.
1
Operation enabled
Enable electronics and pulses, then ramp up
to active setpoint
0
Operation disabled
1
-
0
-
1
No OFF2 active
0
An OFF2 command is present.
1
No OFF3 active
0
An OFF3 command is present.
1
Switching on inhibited
Switching back on is only possible by means
of OFF1 and then ON.
0
No switching on inhibited
Switching on is possible.
1
Ready for switching on
Power supply on, electronics initialized, line
contactors are open, pulses inhibited
0
Not ready for switching on
1
Controller enabled
0
Controller inhibited
1
The automation system is requested to as-
sume control.
0
Control is only possible at the unit itself
1
-
0
-
1
Pulses enabled
0
Pulses inhibited
1
-
0
-
1
-
0
-
1
-
0
-
Operation
Parameter
BO: r0899.0
BO: r0899.1
BO: r0899.2
-
BO: r0899.4
BO: r0899.5
BO: r0899.6
BO: r0899.7
BO: r0899.8
BO: r0899.9
-
BO: r0899.11
-
-
-
143