Function diagrams and parameters
Function diagrams (see SINAMICS DCP List Manual)
● 8560 Command data sets (CDS)
Overview of important parameters (see SINAMICS DCP List Manual)
Adjustable parameters
● p0170 Command data sets (CDS) number
● p0809 Copy command data set (CDS)
● p0810 BI: Command data set CDS bit 0
Using data sets
Copying a command data set
Set parameter p0809 as follows:
1. p0809[0] = Number of the command data set to be copied (source)
2. p0809[1] = Number of the command data set to which the data is to be copied (target)
3. p0809[2] = 1
Copying is started.
Copying is finished when p0809[2] = 0.
Copying a drive data set
Drive data sets are not used with the SINAMICS DCP.
8.1.1.3

Drive objects

A drive object is a self-contained software function with its own parameters and potentially its
own faults and alarms. Drive objects can be provided as standard (e.g. drive control), or can
be created individually or also created several times.
Properties of a drive object:
● Separate parameter space
● Separate window in STARTER
● Separate fault/alarm system
● Separate PROFIdrive telegram for process data
SINAMICS DCP
Operating Instructions, 05/2016, A5E34382853K
Operation
8.1 Operation
111