Note
The functionality of the undervoltage/overvoltage protection is used to protect the battery and
the DC link. For further details, see Chapter Closed-loop control (Page 232) at Voltage
limitation.
〈6〉 Settings for current control
p55050, signal source for the current setpoint (WE = r2050[1])
p55060 meaning of the current setpoint (11 = current on side 1, 12 = current on side 2)
p55220[0] and [1] current controller gain Kp on positive or negative current
(WE = 0.200)
p55221[0] and [1] current controller integral time Tn on positive or negative current
(WE = 5.000)
〈7〉 Settings for voltage control
p54105 signal source to activate the voltage control (WE = 0)
p54100 signal source for the voltage setpoint (WE = 100%)
p54141 signal source for the positive current limit (WE = r522002 = 200%)
p54142 signal source for the negative current limit (WE = r522004 = -200%)
p54125 voltage controller gain Kp (WE = 2.000)
p54126 voltage controller integral time Tn (WE = 0.30 ms)
SINAMICS DCP
Operating Instructions, 05/2016, A5E34382853K
7.2 Commissioning using the BOP20 operator panel
Commissioning
77