Siemens sinamics dcp Operating Instructions Manual page 267

Dc/dc power converter
Hide thumbs Also See for sinamics dcp:
Table of Contents

Advertisement

Commissioning
1. Parameters to be permanently set The following parameters must be set to the values
specified here:
– p54010 = r55540
– p54013 = r55125.11
– p54014[0] = r899.1
– p54014[2] = r55125.7
– p55050 = r54021
2. Adapting to the system configuration
The following values must either be set specifically for the system or set to the values
specified here:
– p54009 = -1.0 (direction of power flow from side 2 to side 1)
– p54000 = 100 % (signal source for setpoint in manual operation)
– p54001 = 1 (signal source for selecting automatic operation)
– p54002 = 100 % (signal source for current setpoint)
– p54005 = 2.000 s (search interval)
– p54006 = 1% (current stage)
– p54007 = 0.9 (current reduction factor)
– p54011 = 0 s (smoothing time power)
– p54030.0 = 1 (characteristic curve recording active)
– p54035 = 300 s (characteristic curve recording interval)
– p54036 = 2 s (characteristic curve recording time)
– p54037 = 10% (search range)
– p55060 = 12 (current on side 2)
SINAMICS DCP
Operating Instructions, 05/2016, A5E34382853K
Operation
8.16 Technological functions
267