Siemens sinamics dcp Operating Instructions Manual page 249

Dc/dc power converter
Hide thumbs Also See for sinamics dcp:
Table of Contents

Advertisement

RDY
DP1
Red
Red
0.5 Hz
0.5 Hz
Orange
Off
Response of the LEDs after ramp-up
Table 8- 35
CUD - Description of the LEDs after ramp-up
LED
Color
RDY (READY) -
Green
Red
Orange
Green/
orange or
red/
orange
DP1
-
PROFIdrive
cyclic opera-
tion
Green
SINAMICS DCP
Operating Instructions, 05/2016, A5E34382853K
LED
OPT
MOD
Off
Off
Off
Off
State
Description, cause
Off
Electronic power supply is missing or outside
permissible tolerance range.
Continuous
The component is ready for operation. No errors
light
are present.
0.5 Hz
Commissioning/reset
flashing
light
2 Hz flash-
Writing to memory card or internal flash memory
ing light
Notice!
The electronic power supply for the SINAMICS
DCP must not be switched off during this write
process.
Switching off the electronic power supply can
lead to the loss of the parameter assignments.
See also Chapter Memory card functions
(Page 113).
2 Hz flash-
General errors
ing light
0.5 Hz
Updating the firmware of the DRIVE-CLiQ com-
flashing
ponents.
light
2 Hz flash-
DRIVE-CLiQ component firmware update com-
ing light
plete. Wait for POWER ON for the respective
components.
1 Hz flash-
Component detection via LED is activated
ing light
(p0124[0]).
Note:
Both options depend on the LED state when
component detection is activated via
p0124[0] = 1.
Off
Cyclic communication has not (yet) taken place.
Note:
The PROFIdrive is ready to communicate when
the CUD is ready for operation (see LED RDY).
Continuous
Cyclic communication is taking place.
light
State
CRC error
Drive initialization
8.14 Diagnostics
Remark
Firmware checked, CRC error
-
Remedy
Check power supply
-
-
-
Check parameteriza-
tion/configuration
Carry out POWER ON for
the respective components
-
-
-
Operation
249

Hide quick links:

Advertisement

Table of Contents
loading