Siemens sinamics dcp Operating Instructions Manual page 48

Dc/dc power converter
Hide thumbs Also See for sinamics dcp:
Table of Contents

Advertisement

Electrical connection
6.4 Terminals and connectors
120 kW device
Recommended connection cable:
● Cable with shield:
SIENOPYR(90) (N)HXSGAFCHXÖ 1.8/3 kV
Cross section: 50 mm
Order no.: 5DF9 660
● Cable without shield:
SIENOPYR(90) (N)HXSGAFHXÖ 1.8/3 kV
Cross-section: 50 mm
Order no.: 5DF8 153
Ground connection
The device must be grounded. The device has a ground connection, identified by a
grounding symbol.
30 kW device: Tightening torque of the screw for the protective conductor: 6 Nm.
120 kW device: Tightening torque of the screw nut for the protective conductor: 13 Nm.
48
2
2
Operating Instructions, 05/2016, A5E34382853K