Siemens sinamics dcp Operating Instructions Manual page 286

Dc/dc power converter
Hide thumbs Also See for sinamics dcp:
Table of Contents

Advertisement

Technical data
B.1 Ambient conditions
Installation altitude above sea level
≤ 2000 m
> 2000 m
Additional properties
The input side (side 1, terminals P1/N1) of the device is connected to a DC link in a normal
application.
● The DC link does not have to be grounded. (for a 30 kW device from product version 02).
● The device input side must be connected (precharging circuit, fuse) as described in
Chapter EMC-compliant installation of SINAMICS DCP (installation instructions)
(Page 38).
The output side (side 2, terminals P2/N2) of the device is connected to a battery in a normal
application.
● The device output side must be connected (precharging circuit, fuse) as described in
Chapter Electrical connection (Page 35).
● Parallel connection
Several devices can be connected in parallel on the input side, the output side or on both
sides simultaneously.
For more information, refer to Chapter Parallel connection of multiple SINAMICS DCPs
(Page 269).
286
With rated DC current
With derating, see Chapter Derating (Page 244).
Operating Instructions, 05/2016, A5E34382853K
SINAMICS DCP