Device Data; B.2 Device Data - Siemens sinamics dcp Operating Instructions Manual

Dc/dc power converter
Hide thumbs Also See for sinamics dcp:
Table of Contents

Advertisement

B.2

Device data

Table B- 2
Technical specifications of the 30 kW device
Variable
Rated voltage
Rated direct current
Rated output
Maximum power loss
Min. operating voltage
Max. operating voltage
Overvoltage range
Overvoltage category
Recurring peak voltage
Protection class
Max. input current
Max. input power
Monitoring
Electronic power supply
Degree of protection
Use
Type of cooling
Fan air flow
Fan noise level
Dimensions (W x H x D)
Weight (approx.)
SINAMICS DCP
Operating Instructions, 05/2016, A5E34382853K
Value
V
600
A
50
kW
30
W
800
V
30
V
800
V
800 - 1000
II
III
V
940
I
A
50
kW
30
V
24
IP20
Forced ventilation
m
/h
300
3
dBA
73
mm
600 x 150 x 545
kg
38
Remark
Applies for input and output
Applies for input and output
Applies for input and output;
operation is possible in this range for 30 s after switch-
on with reduced current (5 A at 1000 V)
between P1 and N1 and between P2 and N2
P1, N1, P2, N2 against enclosure / ground
between the DC mains connections (P1, N1, P2, N2)
and enclosure / ground (according to IEC 60664-
1:2007)
In the voltage range 30 V ... 600 V
In the voltage range 600 V ... 800 V
The device shuts down by means of hardware moni-
toring for voltages greater than 1000 V and for cur-
rents greater than 60 A.
The device can generate a maximum short-circuit
current of 60 A.
Power consumption: 5 A
Exclusively for cabinet installation
Pollution degree 2
Technical data

B.2 Device data

287

Hide quick links:

Advertisement

Table of Contents
loading