Mitsubishi GOT1000 GT15 User Manual page 552

Graphic operation terminal
Hide thumbs Also See for GOT1000 GT15:
Table of Contents

Advertisement

Error
code
595 Logging file error.
Logging setting does not
596
exist or setting value
error.
The specified logging ID
597
does not exist.
The specified logging
598
setting is incompatible.
Unsupported version of
600
printer unit.
601 Printer unit error.
Video/RGB unit not
602
mounted
603 External I/O unit error
604 Sound output unit error
Insufficient memory
610
capacity.
Improper job files.
611
Confirm job setting.
Cannot access Logging
612
Files Check the memory
card
20
20.3 ERROR MESSAGE AND SYSTEM ALARM
- 32
20.3.2 List of Error Message/System Alarm
Error message
Logging file error.
When collecting data again, delete logging files and
management files.
The logging setting specified in the historical trend graph
setting does not exist.
Review the historical trend graph setting and specify a logging
setting that exists.
Check the logging ID in the historical trend graph setting.
1. When setting the logging, enter an existing logging ID.
2. When setting the logging ID by using a device or the
1. Configure the setting so that the number of logging
2. Configure the setting so that the data type of the logging
The version of OS installed in the GOT is not compatible with
the printer unit.
Install the extended function OS (Printer) with the latest GT
Designer3 or GT Designer2.
The printer unit is installed incorrectly. The built-in flash
memory of the printer unit is broken or the guaranteed life has
been elapsed.
Check that the printer unit is installed correctly.
When the printer unit has been installed correctly, the built-in
flash memory is broken or the guaranteed life has been
elapsed. Replace the printer unit with new one.
1. Check if the video/RGB input unit is installed.
2. Check if the GOT used supports video/RGB input.
Check if the external I/O unit is correctly installed.
Check if the sound output unit is correctly installed.
The memory capacity for the MES interface function is
insufficient.
Delete unnecessary files, and reserve memory.
The contents for job files are unmatched with the settings for
job files.
Check if there are mistakes in the settings on the setting
screen.
1. Insert a memory card.
2. Turn on the memory card access switch.
3. If the memory card has unnecessary files, delete the files.
Action
graph offset function, specify the device for the logging ID
set in the logging setting.
devices set for the logging ID exceeds that of data lines on
the historical trend graph.
device set for the logging ID is the same as that of the
device specified in the historical trend graph.
Channel
No.
storage

Advertisement

Table of Contents
loading

This manual is also suitable for:

Got 1000Gt15

Table of Contents