7.6 Grounding Extension Units

7.6.1

Wiring FG cable of bus connection cable

This section describes wiring of the FG cable when a PLC CPU is connected to the GOT.
Cable connected to the PLC CPU
1
When connecting QCPU or motion controller CPU (Q series) to the GOT
• Grounding of the FG cable for QCPU and motion controller CPU (Q series) is not necessary since they
have no FG wire.
2
When connecting QnACPU, ACPU, or motion controller CPU (A series) to the GOT
• When using GT15-C
(1) GOT terminal block
(2) Ground cables
Do not install the connection cable together with the main circuit lines (high voltage,
large current) or I/O signal lines.
EXSS-1 or GT15C
BS, perform the grounding in the following steps.
The terminal block layout of a GOT differs depending on the model.
Before wiring, check the terminal layout of the GOT to be used.
Up to two ground cables can be connected to the LG and FG terminals of the
GOT respectively.
For three or more ground cables, connect the third or later ground cables to the
LG terminal.
7.6 Grounding Extension Units
7.6.1 Wiring FG cable of bus connection cable
1
2
3
4
5
6
7
8
7
- 13