Advertisement

(5) CC-Link IE Field Network connection and Ethernet connection
• Strip the outer insulation layer at both ends of the cable by the length shown below to expose the
braided shield for grounding. (For grounding with cable clamps. (refer to Section 5.4.3.))
• Attach the ferrite core to the cable in the position as illustrated below.
GOT side
120 or
less
(4.72)
230 or less
(9.06)
(6) External I/O device connection
• Strip the outer insulation layer at both ends of the cable by the length shown below to expose the
braided shield for grounding.(For grounding with cable clamps (Refer to Section 5.4.3.))
• Connect the braided shield to the connector with the connector cover.
• Twist power cables.
GOT side
Braided shield
Connector cover
360 or less
(14.17)
5.4 Precautions for Wiring/Connecting the EMC Directive-Compliant Product
Ferrite Core
(ZCAT3035-1330)
40
(1.57)
Power cable
40
(1.57)
Controller side
40
400 or less
(15.75)
(1.57)
External I/O device side
40
360 or less
(14.17)
(1.57)
5.4.2 Processing connection cables
1
2
3
Unit : mm (inch)
4
5
Unit : mm (inch)
6
7
8
5
- 21