Mitsubishi GOT1000 GT15 User Manual page 543

Graphic operation terminal
Hide thumbs Also See for GOT1000 GT15:
Table of Contents

Advertisement

Error
Error message
code
Error in specified PLC
357
drive Confirm PLC drive
PLC file access failure.
358
Confirm PLC drive.
Processing from another
359
peripheral device.
Execute it after.
0 divisor division error.
360
Confirm operation
expression.
Specified device No. is
361
out of range.
Invalid device value in
362
time action setting
Upper and lower limit
370
value error. Confirm value
setting.
Action
When executing the recipe function specifying the file register
name, error occurred in PLC CPU drive.
1. Execute the recipe function again after confirming the
specified PLC CPU drive.
2. Execute the recipe function again after formatting the PC
memory in the specified PLC CPU drive with GX
Developer.
When the recipe function is executed specifying the file
register name, PLC CPU file register could not be accessed.
1. Execute the recipe function again after confirming the
specified PLC CPU drive / file register name. (When you
specify drive 0, execute the recipe function again after
changing to other drives.)
2. Confirm whether the memory card is write-protected, and
execute the recipe function again.
3. Confirm that the security key is not set on the specified
CPU, and execute the recipe function again.
When the recipe function is executed specifying the file
register name, other peripherals carry out the process to the
file register.
Wait until the processing of other peripherals end, and
execute the recipe function again.
Zero division occurred by the data operational expression.
Review the data operational expression so that the divisor
should not become 0.
The entered file number is out of range.
Check the entered file number, and enter a valid value (1 to
9999).
When controllers are controlled with the GOT's time action
function, the set No. is our of range, or the set device values
regarding the operation settings are out of range or invalid.
Set valid values.
The setting of lower/upper limit value is [Upper limit < Lower
limit].
Correct the setting so as to be "Upper limit
20.3 ERROR MESSAGE AND SYSTEM ALARM
20.3.2 List of Error Message/System Alarm
Channel
No.
storage
Lower limit".
20
- 23
17
18
19