(1) When using GT15-C
(2) When using GT15-C
For the both side GOTs, connect the LG and FG terminals of the terminal block on the GOT unit
power and ground them with a cable.
7
7.6 Grounding Extension Units
- 14
7.6.1 Wiring FG cable of bus connection cable
EXSS-1
PLC
FG
LG
(GT15-EXCNB)
N
L
1
Connect the LG and FG terminals of the terminal block on the GOT unit power
and ground them with a cable.
2
Use the GT15-C
BS's FG cable of 28cm or less.
3
Do not connect the GT15-EXCNB's FG ground cable.
4
Connect the GT15-C
power's terminal block.
5
Connect the GT15-C
power supply module.
6
Connect the LG and FG terminals of the terminal block on the PLC and ground
them with a cable.
BS
Not connected
(GT15-C
BS)
2SQ cables to
FG terminals,
28cm or less
BS's FG cable on the GOT side to FG of the GOT unit
BS's FG cable on the PLC side to FG of the PLC's
GOT