Specific Example Of Troubleshooting - Mitsubishi GOT1000 GT15 User Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 GT15:
Table of Contents

Advertisement

20.2.3 Specific example of troubleshooting

Taking the following system as an example, troubleshooting is shown when PLC CPU error occurred. (When
QnASCPU and the extension base unit are used)
Extension cable
The bus-connection cable connecting the GOT 1) to the GOT 2) is judged faulty.
20
20.2 Troubleshooting in Bus Connection
- 16
20.2.3 Specific example of troubleshooting
PLC
(main base unit)
PLC
(extension base unit)
Check the error code/step appearing on the PLC CPU.
(Obtain the status of the error and the location where the error occurs.)
The SP. UNIT DOWN message appears on PLC CPU.
Turn off the power of the GOT.
Turn off the power of the PLC.
Replace the faulty PLC CPU with a new one.
Turn on the power of the PLC.
Turn on the power of the GOT.
The error occurs further (not on PLC CPU).
Turn off the power of the GOT.
Turn off the power of the PLC.
Disconnect the bus-connection cable from the GOT 2) at IN side
(to further locate the error positions).
Turn on the power of the PLC.
Turn on the power of the GOT.
The error occurs further
(not on the GOT 2) (bus connection unit)).
Turn off the power of the GOT.
Turn off the power of the PLC.
Disconnect the bus-connection cable from the GOT 1) at OUT side
(to further locate the error positions).
Turn on the power of the PLC.
Turn on the power of the GOT.
The error will not occur.
Replace the faulty bus-connection cable with a new one.
GOT 1)
Bus connection
Bus connection
cable
cable
Start
End
GOT 2)