19.5 Backlight Shutoff Detection and Replacement

The backlight is built into GOT for the liquid crystal display.
When GOT detects backlight shutoff, the POWER LED blinks green/orange alternately.
The brightness of the backlight decreases with the lapse of usage period. When backlight shutoff is detected
or the display becomes unclear, replace the backlight.
When replace the backlight, refer to "19.6 Backlight Replacement".
(1) Life of backlight
The usable duration of backlight can be extended by setting to [Screen saving backlight off] in the
utility of GOT (GOT set up).
Refer to the following for details.
11. DISPLAY AND OPERATION SETTINGS (GOT SET UP)
(2) Replacement time of backlight
The backlight replacement time can be set by the utility of GOT (Maintenance timing setting) with
reference to the life of backlight.
Refer to the following for details.
16. MAINTENANCE TIME NOTIFICATION SETTING (MAINTENANCE TIMING
SETTING)
Moreover, when system alarm is used, the message that notifies of the backlight replacement time can be
displayed on the GOT screen.
502 Warning! Backlight needs replacement soon.
Refer to the following for the system alarm display.
• GT Designer3 Version1 Screen Design Manual (Functions) (10. ALARM)
• GT Designer2 Version
Precautions for the backlight shutoff status
Screen Design Manual (8. ALARM)
In the backlight shutoff status, the touch key operates.
Early replacement of backlight is recommended.
19.5 Backlight Shutoff Detection and Replacement
System alarm
17
18
19
20
19