6.4 Control Panel Inside Temperature and Mounting
Angle
When mounting the main unit to a control panel or similar, set the display section as shown below.
When the temperature inside the control panel is 40 to 55°C or less, the mounting angle should be in the
range 60 to 105 degrees.
Display
section
Control panel,
etc.
• The GOT will be deteriorated earlier if it is used at the mounting angle other than the above. Therefore,
the temperature inside the control panel should be within 40°C.
*:
When mounting MELSECNET/H communication unit (GT15-J71LP23-25, GT15-J71BR13) or CC-Link
communication unit (GT15-J61BT13), the operating ambient temperature must be reduced 5°C against the
maximum values described in general specifications.

6.5 Installation Procedure

The GOT mounting procedure is as follows.
For the panel cutting dimensions of each GOT, refer to the following.
6.2 Panel Cutting Dimensions
1
Insert the GOT into the panel opening from the front side.
GOT
GOT

6.4 Control Panel Inside Temperature and Mounting Angle

105°
60°
panel opening
1
2
3
4
5
6
7
8
6
- 11