(4) Unit error information
Displays the number of unit errors and the error codes.
No.
(6)
Unit error
(7)
ErrCode
(5) Link scan time information
Displays the link scan time.
No.
Current LS time
Max. LS time
(8)
Min. LS time
Constant LS time
(6) Host station line status
Displays the connection status of the CC-Link IE Field Network communication unit.
No.
Connection
(9)
PORT1: cable disconnct count 0: No error, 1 or more: Number of accumulated errors
PORT1: line err count
PORT2: cable disconnct count 0: No error, 1 or more: Number of accumulated errors
PORT2: line err count
14
14.8 NETWK Unit Status Display
- 32
14.8.3 Display example of the NETWK unit status display
Item
Displays the number of module errors.
Error histories of 16 errors are displayed in 16 lows from the latest.
Item
Displays the current link scan time.
Displays the maximum link scan time.
Displays the minimum link scan time.
Displays the link scan time set in the parameter.
Item
Displays the connection status of the host station.
Normal (PORT1: communicating, PORT2: communicating)
Normal (PORT1: communicating, PORT2: cable disconnected)
Normal (PORT1: in loopBK communication, PORT2 cable disconnected)
Normal (PORT1: cable disconnected, PORT2: communicating)
Normal (PORT1: cable disconnected, PORT2: in loopBK communication)
Disconnect (PORT1: cable disconnected, PORT2: cable disconnected)
Disconnect (PORT1: cable disconnected, PORT2: connecting a line)
Disconnect (PORT1: connecting a line, PORT2: cable disconnected)
Disconnect (PORT1: connecting a line, PORT2: connecting a line)
0: No error, 1 or more: Number of accumulated errors
0: No error, 1 or more: Number of accumulated errors