Install the Wall-Mounting Plates
The top plate is used for mounting the back-up battery. The bottom plate is used to mount the power
supply and distribution units. The plates can be rack-mounted using standard rack-mounting brackets.
See
1145B2/1146B2 Mounting Arrangement
1
Locate one plate directly below the other one such that the AC power cord (6.5 feet [2 meters])
reaches the electrical outlet from a power supply mounted on the bottom plate. Both plates should
be located so the raised letters are right side up.
NOTE:
A maximum of four power supplies can be powered from one dedicated 110 volts AC,
20 amperes (or 230 volts AC, 15 amperes) feeder. Use only nonswitched outlets (outlets
not connected to a wall switch).
2
Secure the wall mounting plates to a standard 3/4-inch (2 centimeters) thick plywood mounting
board. Each mounting plate comes with four #10 x 1/2-inch wood screws.
3
The 1145B2 Power Supply is snap-fit onto the bottom wall mounting plate without tools.
4
An installer-provided insulated ground wire, 16 AWG (#12) (1.2 square millimeters) or greater, is
required to connect the power supply frame ground lug to an approved ground. The frame ground
screw is located next to the AC outlet, to the left of the unit.
Mount the 1146B2 Power Distribution Unit
See the 1146B2 Power Distribution Unit in
1
Insert and securely tighten the two supplied #8-32 x 1/2-inch shoulder screws (they have an
unthreaded section at the top) into the top holes designated for 1146B2 Power Distribution Unit
on the bottom plate. Mount the unit on these two shoulder screws, using the key holes on the back
of the unit.
2
Secure the unit by inserting the #8-32 x 1-inch screw through the bottom of the unit (just above
the wire clips) into the plate and tighten.
3
Set the battery back-up switch option to the 1-32 (down) position to provide battery back-up to all
outputs.
4
Connect the power distribution unit to the power supply with the power cable. Refer to the power
supply's right-hand label to locate the output power connection.
Install the Battery Mounting/Wiring
Three types of back-up batteries are used. See
battery type and rating.
1
Insert two #10-32 x 1/2-inch shoulder screws into the top designated battery holes on the wall
mounting plate. Lightly screw in but do not tighten.
2
Place the keyhole slots in the battery bracket on these two screws. The battery cord exits from the
right of the bracket. Make sure the label on the battery is visible. Tighten the screws securely.
3
Plug the battery cord into the power supply's right rear receptacle. The rear receptacle is indicated
on the right label.
Installation, Upgrades and Additions for Avaya CMC1 Media Gateways
June 2004
Installing and Cabling the Cabinets
Install and Wire Telephone Power Supplies
on page 87.
Expanded Power Distribution Unit
Table 14, Back-Up Battery Rating,
on page 88.