Install Off-Premises Station Wiring - Avaya CMC1 Installation Manual

Installation, upgrades and additions for media gateways
Table of Contents

Advertisement

Installing and Cabling the Cabinets

Install Off-Premises Station Wiring

Install Off-Premises Station Wiring
The cabling for off-premises stations is provided by the local telephone company. These stations can
appear on any of the RJ21X network interfaces provided for the CO trunks.
CAUTION:
Use only an FCC-approved (or equivalent) analog type telephone (such as a 2500-type) as
an off-premises station. The TN746B and TN2183 Analog Line circuit packs can be
connected to off-premises stations.
1
Install an A25D cable between the RJ21X network interface and a sneak fuse panel.
2
At the MDF, connect jumper wires between 1 row/connecting block in the green field and up to 3
rows/connecting blocks in the purple field to concentrate the analog line pairs.
3
Connect an A25D cable between the sneak fuse panel and the terminal block connector associated
with the green row in Step 2.
4
Install a green label on the terminal block to identify the remote location.
5
Administer per Administrator's Guide for Avaya Communication Manager.
Install Off-Premises or Out-of-Building
Stations
Out-of-building campus stations are those telephones not physically located in the same building as the
equipment room but are located on the same property.
Analog Off-Premises Stations
Figure 62, Connections for 1 to 8 Out-of-Building Analog Telephones,
connections for 1 to 8 off-premises analog telephones. Only analog telephones connected to TN746B,
TN2183, or TN769 Analog Line circuit packs can be installed out-of-building.
The maximum distance from the system cabinet to the out-of-building voice terminal is 6000 feet (1828.8
m) using 24 AWG (#5) (0.26 mm
116
2
) wire.
Installation, Upgrades and Additions for Avaya CMC1 Media Gateways
on page 117 shows the