Mitsubishi NZ2GFCF-D62PD2 User Manual page 277

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

(13)Module-based monitoring data (address: 0620
Address
Name
CH1
CH2
0620
0640
Operation mode
H
H
Selected counter
0621
0641
H
H
function
Description
• This area stores the present operation mode.
• The following shows the range of values which can be stored.
0: Normal Mode
1: Frequency Measurement Mode
2: Rotation Speed Measurement Mode
3: Pulse Measurement Mode
4: PWM Output Mode
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
• This area stores the counter function currently valid.
• The following shows the range of values which can be stored.
0: Count Disable Function
1: Latch Counter Function
2: Sampling Counter Function
3: Periodic Pulse Counter Function
4: Count disable/Preset/replace Function
5: Latch counter/Preset/replace Function
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
to 0621
, 0640
to 0641
H
H
H
APPENDICES
)
H
Default
0
A
0
275

Advertisement