(2) Performing the preset/replace function by CH Phase Z input terminal (Z1, Z2)
The preset/replace function by CH Phase Z input terminal (Z1, Z2) can be performed when the set trigger
condition is met.
(a) Setting method of the condition for the preset/replace function by CH Phase Z
input terminal (Z1, Z2)
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window
2.
Set "CH Z phase (Preset) trigger setting".
3.
Set "CH External preset/replace (Z Phase) request detection setting".
124
[CC IE Field Configuration]
Select a high-speed counter module in "List of stations"
[Parameter Processing of Slave Station]