Mitsubishi NZ2GFCF-D62PD2 User Manual page 212

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

Error code
Classification
(hexadecimal)
0140
Minor error
H
0150
Minor error
H
0160
Minor error
H
0330
Moderate error
H
0340
Moderate error
H
0800
Moderate error
H
0850
Moderate error
H
0F40
Moderate error
H
1341
Moderate error
H
210
Description and
Error name
cause
Non-volatile
The error history data
memory data
stored in the nonvolatile
error
memory are abnormal.
(error history)
The REMFR/REMTO
Remote buffer
instruction has accessed
memory access
the range outside the
error
remote buffer memory
range.
The setting on the station
Station number
number setting switch has
switch change
been changed while the
failure
module power supply is
on.
Number of ON
The number of ON times
times
integration function is
integration
enabled when the cam
function setting
switch function is selected.
error
A value other than 0 and 1
Cam switch
is set in Cam switch output
output unit
unit assignment setting
assignment
(address: 0104
setting error
The setting in Comparison
output setting (address:
0100
) is in one of the
H
following cases.
Comparison
• A value other than 0 and
output setting
1 is set.
error
• If 1 is set, the value in
CH Operation mode
setting (address: 0120
0140
) is other than 0.
H
A value other than 0 to 20
Cyclic data
is set in Cyclic data update
update watch
watch time setting
time setting
(address: 0003
error
The lower 3 bits of Input
Input response
response time setting
time setting
(address: 0001
error
000b, 001b, or 010b.
An extension output
module does not exist
Cam switch
where Cam switch output
output unit
unit assignment setting
assignment
(address: 0104
error
the module.
Operation of when an error
occurs
Error CH
*1
*1
*1
*13
*13
).
H
*13
,
H
*13
).
H
*13
) is set to
H
*13
) assigns
H
Action
The other
CHs
• The module recovers
automatically soon after this
error occurred. However, the
preceding error history data
are erased.
• Take measures against
noise, such as using a
shielded cable for
connection.
• If the same error occurs
again, a module failure may
be the cause. Please consult
your local Mitsubishi
representative.
Correct the REMFR/REMTO
instruction setting so that the
instruction accesses the range
within the remote buffer
memory range.
Set the switch back to the
station number which was set
when the module was powered
on.
Set Number of ON times
integration function enable
(address: 0202
) to 0000
H
turn off then on Initial data
setting request flag (RY9).
Set Cam switch output unit
assignment setting (address:
0104
) to 0 or 1, and turn off
H
then on Initial data setting
request flag (RY9).
Take the following actions, and
turn off then on Initial data
setting request flag (RY9).
• Set Comparison output
setting (address: 0100
or 1.
• Set CH Operation mode
setting (address: 0120
0140
) to 0.
H
Set Cyclic data update watch
time setting (address: 0003
a value between 0 and 20, and
turn off then on Initial data
setting request flag (RY9).
Set the lower 3 bits of Input
response time setting (address:
0001
) to a value other than
H
000b, 001b, and 010b, then
turn on Initial data setting
request flag (RY9).
Power off the module, and
connect an extension output
module where Cam switch
output unit assignment setting
(address: 0104
) assigns the
H
module. Then power on the
module.
, and
H
) to 0
H
,
H
) to
H