(6) Remote registers (RWr21 to RWr23, RWr39 to RWr3B)
Address
(RWr)
Item
CH1 CH2
21
39
External input status
22
3A
Latest error code
23
3B
Latest warning code
260
• This area stores the input statuses of phase Z, the function, the latch counter,
phase A, and phase B of the external I/O connector.
b15
b14
b13
b12
b11
b10
b9
0
0
0
0
0
0
0
0 (fixed)
• When CH Operation mode setting (address:0120
Frequency Measurement Mode (1), Rotation Speed Measurement Mode (2),
or PWM Output Mode (4), Function input status (RWr21.b1, RWr39.b1) is
always OFF (0).
• With Negative Logic (1) being set in CH Function input logic setting
(address: 0127
, 0147
) or CH Latch counter input logic setting (address:
H
H
0128
, 0148
), its input status changes to OFF (0) when a voltage is applied.
H
H
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
• This area stores the latest error code of the generated major error or
moderate error.
• When multiple errors in the same category occur, this area stores the error
code of the later error.
• When a moderate error occurs while a major error is occurring, this area does
not store the error code of the moderate error.
• For the error code, refer to Page 208, Section 11.2.
• This area stores the error code of the generated minor error.
• When multiple minor errors occur, this area stores the error code of the later
error.
• For the error code, refer to Page 208, Section 11.2.
Description
b8
b7
b6
b5
b4
b3
b2
b1
0
0
0
0
, 0140
H
Default
b0
Phase Z input
status
0: OFF
1: ON
Function input
status
0: OFF
1: ON
Latch counter
input status
0: OFF
1: ON
Phase A input
0000
status
H
0: OFF
1: ON
Phase B input
status
0: OFF
1: ON
) is set to either of