Mitsubishi NZ2GFCF-D62PD2 User Manual page 275

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

(10)Module-based parameter data (address: 0129
Address
Name
CH1
CH2
External control
0129
0149
input response time
H
H
setting
Description
• Set the input response time of CH Phase Z input terminal (Z1, Z2), CH
Function input terminal (FUNC1, FUNC2), and CH Latch counter input
terminal (LATCH1, LATCH2).
• The following shows the setting range.
b15
b14
b13
b12
b11
b10
b9
0
0
0
0
0
0
0
0 (fixed)
1) Z phase input response time setting
Setting
Response time
00
0.25µs
01
0.1ms
10
1.0ms
2) Function input response time setting
Setting
Response time
00
0.02ms
01
0.1ms
10
1.0ms
3) Latch counter input response time setting
Setting
Response time
00
0.02ms
01
0.1ms
10
1.0ms
• When CH Function input logic setting (address: 0127
Latch counter input logic setting (address: 0128
Negative Logic (1), the OFF → ON response time and the ON → OFF
response time invert. For example, when CH Latch counter input logic
setting (address: 0128
, 0148
H
H
corresponding bits for this area are set to 00, the OFF → ON response time
is 0.1ms.
• The reflection timing of the setting value
When Initial data setting request flag (RY9) is turned off then on
, 0149
)
H
H
b8
b7
b6
b5
b4
b3
b2
0
0
0
3)
2)
OFF → ON
ON → OFF
Response time
2.5µs
0.1ms
1.0ms
OFF → ON
ON → OFF
Response time
0.1ms
0.1ms
1.0ms
OFF → ON
ON → OFF
Response time
0.1ms
0.1ms
1.0ms
, 0147
H
H
, 0148
) are set to
H
H
) is set to Negative Logic (1) and
APPENDICES
Default
b1
b0
1)
002A
H
) and CH
273
A