(8) Remote registers (RWw2 to RWwF)
Address
(RWw)
Item
CH1 CH2
Upper limit value
2
setting
3
(Coincidence output 1)
Point setting
(Coincidence output 2)
4
Lower limit value
5
setting
(Coincidence output 2)
Upper limit value
6
setting
7
(Coincidence output 2)
Point setting
(Coincidence output 3)
8
Lower limit value
9
setting
(Coincidence output 3)
Upper limit value
A
setting
B
(Coincidence output 3)
Point setting
(Coincidence output 4)
C
Lower limit value
D
setting
(Coincidence output 4)
Upper limit value
E
setting
F
(Coincidence output 4)
262
• When the coincidence output function is selected and a bit corresponding to
Coincidence output 1 of Coincidence output comparison condition setting
(address: 0102
) is set to "Within-range Output (01)" or "Out-of-range Output
H
(10)", set the upper limit value.
• When a bit corresponding to Coincidence output 1 of Coincidence output
comparison condition setting (address: 0102
(00)", this setting value is not used.
• The following shows the setting range.
-2147483648 to 2147483647
• The reflection timing of the setting value
1)
When Initial data processing request flag (RX8) turns off
2)
When Initial data setting request flag (RY9) is turned off then on (only while
Initial data processing request flag (RX8) is off)
3)
When Setting change request (Coincidence output 1) (RY14) is turned off
then on
• This setting is for Coincidence output 2 of the coincidence output function.
• The details on this area such as the setting range are the same as those of
Point setting (Coincidence output 1)/Lower limit value setting (Coincidence
output 1) (RWw0 to RWw1) except the coincidence output number.
• This setting is for Coincidence output 2 of the coincidence output function.
• The details on this area such as the setting range are the same as those of
Upper limit value setting (Coincidence output 1) (RWw2 to RWw3) except the
coincidence output number.
• This setting is for Coincidence output 3 of the coincidence output function.
• The details on this area such as the setting range are the same as those of
Point setting (Coincidence output 1)/Lower limit value setting (Coincidence
output 1) (RWw0 to RWw1) except the coincidence output number.
• This setting is for Coincidence output 3 of the coincidence output function.
• The details on this area such as the setting range are the same as those of
Upper limit value setting (Coincidence output 1) (RWw2 to RWw3) except the
coincidence output number.
• This setting is for Coincidence output 4 of the coincidence output function.
• The details on this area such as the setting range are the same as those of
Point setting (Coincidence output 1)/Lower limit value setting (Coincidence
output 1) (RWw0 to RWw1) except the coincidence output number.
• This setting is for Coincidence output 4 of the coincidence output function.
• The details on this area such as the setting range are the same as those of
Upper limit value setting (Coincidence output 1) (RWw2 to RWw3) except the
coincidence output number.
Description
) is set to "Coincidence Output
H
Default
0
0
0
0
0
0
0