(4) Remote registers (RWr18 to RWr1F, RWr30 to RWr37)
Address
(RWr)
Item
CH1 CH2
Latch count value
18
30
(Latch counter input
19
31
terminal)
Measured frequency
value
1A
32
1B
33
Measured rotation
speed value
Measured pulse value
1C
34
(Function input
1D
35
terminal)
Measured pulse value
1E
36
(Latch counter input
1F
37
terminal)
258
• This area stores the count value latched when the latch counter function by
latch counter input terminal is selected.
(For the overview of the operation, refer to Page 127, Section 8.5.)
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
• This area stores the frequency value measured when the frequency
measurement function is selected.
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
• This area stores the rotation speed value measured when the rotation speed
measurement function is selected.
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
• This area stores the value of the ON width or OFF width of pulses input to
CH Function input terminal (FUNC1, FUNC2) measured when the pulse
measurement function is selected.
• The following shows the range of values which can be stored.
0 to 2147483647 (increments of 0.1µs)
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
• This area stores the value of the ON width or OFF width of pulses input to
CH Latch counter input terminal (LATCH1, LATCH2) measured when the
pulse measurement function is selected.
• The following shows the range of values which can be stored.
0 to 2147483647 (increments of 0.1µs)
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
Description
Default
0
0
0
0