(a) Method for clearing a warning
Error type
Minor error
*1
A warning results in the following state five seconds after the error cause is removed or CH Error reset command
(RY36, RY4E) is turned off then on.
• Warning status flag (RX7) turns off.
• CH Warning status (RX37, RX4F) of a channel where the error cause is removed turns off.
• CH Latest warning code (RWr23, RWr3B) of a channel where the error cause is removed is cleared.
• The ERR. LED turns off.
Operation to clear Station number switch change failure (error code: 0160
Ex.
CH1 Latest warning code
170
Error code:
Other than
050
Warning
H
Error code:
050
H
Station number
setting switch
Warning status flag
OFF
(RX7)
0
(RWr23)
ERR. LED
OFF
ON
Remote READY
(RXB)
Clearing an error
A warning is cleared five seconds after the error cause is removed.
Turning off then on CH Error reset command (RY36, RY4E) resets
the warning status of each channel.
Controlled by the high-speed counter module
ON
0160
H
(station number switch
change failure)
Flashing
*1
)
H
OFF
0
OFF
5 seconds
*1