Chapter 3 Specifications; General Specifications - Mitsubishi NZ2GFCF-D62PD2 User Manual

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

CHAPTER 3
This chapter describes the specifications of the high-speed counter module.
3.1

General Specifications

Item
Operating
ambient
temperature
Storage ambient
temperature
Operating
ambient humidity
Storage ambient
humidity
Compliant with
Vibration
JIS B 3502 and
resistance
IEC 61131-2
Shock resistance
Operating
atmosphere
Operating
*1
altitude
Installation
location
Overvoltage
*3
category
Pollution
*4
degree
Equipment class
*1
Do not use or store the high-speed counter module under pressure higher than the atmospheric pressure of altitude 0m.
Doing so may cause malfunction. When using the high-speed counter module under pressure, please consult your local
Mitsubishi representative.
*2
If the environment satisfies the operating ambient temperature, operating ambient humidity and other conditions, the
module can be used even outside the control panel.
*3
This indicates the section of the power supply to which the equipment is assumed to be connected between the public
electrical power distribution network and the machinery within premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand
level for the equipment with the rated voltage of 300V or less is 2500V.
*4
This index indicates the degree to which conductive material is generated in terms of the environment in which the
equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must
be expected occasionally.
SPECIFICATIONS
Frequency
Under
5 to 8.4Hz
intermittent
8.4 to 150Hz
vibration
5 to 8.4Hz
Under continuous
vibration
8.4 to 150Hz
Compliant with JIS B 3502 and IEC 61131-2 (147m/s
Specifications
0 to 55°C
-25 to 75°C
5 to 95%RF, non-condensing
Constant
acceleration
2
9.8m/s
2
4.9m/s
2
, 3 times each in X, Y, and Z directions)
No corrosive gases
0 to 2000m
*2
Inside a control panel
II or less
2 or less
Class I

CHAPTER 3 SPECIFICATIONS

Number of
Half amplitude
sweeps
3.5mm
10 times each in
X, Y, and Z
directions
1.75mm
3
25