Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

(2) Program condition
This program uses Coincidence output 1 and Coincidence output 2 of CH1 in the high-speed counter module.
The extension output module is used for outputting digital output signals and cam switch output signals.
(3) Initial setting description
(a) Remote buffer memory (parameter area) setting
Input response time setting
Output HOLD/CLEAR setting
Cyclic data update watch time setting
Comparison output setting
Coincidence output 1 channel assignment setting
Coincidence output 2 channel assignment setting
Coincidence output 3 channel assignment setting
Coincidence output 4 channel assignment setting
Coincidence output 1 comparison condition setting
Coincidence output 2 comparison condition setting
Coincidence output 3 comparison condition setting
Coincidence output 4 comparison condition setting
Preset/replace setting at coincidence output (Coincidence output 1)
Preset/replace setting at coincidence output (Coincidence output 2)
Cam switch output unit assignment setting
Cam switch output 1 channel assignment setting
Cam switch output 2 channel assignment setting
Cam switch output 3 channel assignment setting
Cam switch output 4 channel assignment setting
Cam switch output 5 channel assignment setting
Cam switch output 6 channel assignment setting
Cam switch output 7 channel assignment setting
Cam switch output 8 channel assignment setting
Cam switch output 9 channel assignment setting
Cam switch output 10 channel assignment setting
Cam switch output 11 channel assignment setting
Cam switch output 12 channel assignment setting
Cam switch output 13 channel assignment setting
Cam switch output 14 channel assignment setting
Cam switch output 15 channel assignment setting
Cam switch output 16 channel assignment setting
CH1 Operation mode setting
CH1 Count source selection
CH1 Pulse input mode
CH1 Counting speed setting
CH1 Counter format
CH1 Z phase (Preset) trigger setting
182
Setting item
Setting value
5: 10ms (Initial value)
1: HOLD
10 (× 100ms)
Set a value according to the comparison output function
to be used.
0: CH1 (Initial value)
0: CH1 (Initial value)
1: CH2
1: CH2
0: Coincidence Output (Initial value)
1: Within-range Output
0: Coincidence Output (Initial value)
0: Coincidence Output (Initial value)
0: Present value not replaced (Initial value)
0: Present value not replaced (Initial value)
1: Stage 1
0: CH1 (Initial value)
0: CH1 (Initial value)
0: CH1 (Initial value)
0: CH1 (Initial value)
0: CH1 (Initial value)
0: CH1 (Initial value)
0: CH1 (Initial value)
0: CH1 (Initial value)
1: CH2
1: CH2
1: CH2
1: CH2
1: CH2
1: CH2
1: CH2
1: CH2
Set a value according to the operation mode to be used.
0: A Phase/B Phase (Initial value)
3: 2-Phase Multiple of 1
2: 200kpps
Set a value according to the counter format to be used.
0: Rising (Initial value)