Mitsubishi NZ2GFCF-D62PD2 User Manual page 244

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

Remote input
Signal name
(RX) No.
RX25
CH1
Counter function
detection
RX3D
CH2
RX26
CH1
Cam switch
execute/PWM
output
RX3E
CH2
RX27
CH1
Setting change
completed
(Sampling
counter/Periodic
pulse counter)
RX3F
CH2
242
• This signal turns on when the counter function starts by turning on CH Selected counter
function start command (RY25, RY3D).
• This signal turns off when CH Selected counter function start command (RY25, RY3D) is
turned off.
• The following figure shows an operation example of when the latch counter function is
performed.
Controlled by the high-speed counter module
Controlled by the program
CH
Present value
(RWr10 to RWr11, RWr28 to RWr29)
CH
Selected counter function
start command
(RY25, RY3D)
CH
Latch count value
(RWr12 to RWr13, RWr2A to RWr2B)
CH
Counter function detection
(RX25, RX3D)
• This signal turns on when the cam switch function is started by turning on CH Cam switch
execute command/PWM output start command (RY26, RY3E).
• This signal turns on when the PWM output is started by turning on CH Cam switch
execute command/PWM output start command (RY26, RY3E).
• This signal turns off when CH Cam switch execute command/PWM output start command
(RY26, RY3E) is turned off.
• This signal turns on after the changes of CH Time unit setting (Sampling counter/Periodic
pulse counter) (RWw16, RWw2E) and CH Cycle setting (Sampling counter/Periodic pulse
counter) (RWw17, RWw2F) by CH Setting change request (Sampling counter/Periodic
pulse counter) (RY27, RY3F) are reflected to the high-speed counter module.
• This signal turns off when CH Setting change request (Sampling counter/Periodic pulse
counter) (RY27, RY3F) is turned off.
Controlled by the high-speed counter module
Controlled by the program
CH
Setting change request
(Sampling counter/Periodic pulse counter)
CH
(Sampling counter/Periodic pulse counter)
(Sampling counter/Periodic pulse counter)
CH
Setting change completed
(Sampling counter/Periodic pulse counter)
Description
0
1
2
ON
OFF
0
1
ON
OFF
OFF
(RY27, RY3F)
Time unit setting
0
(RWw16, RWw2E)
CH
Cycle setting
0
(RWw17, RWw2F)
OFF
(RX27, RX3F)
3
4
5
6
4
ON
1
100
ON
7