Error code
Classification
(hexadecimal)
601
Moderate error
H
602
Moderate error
H
621
Moderate error
H
622
Moderate error
H
623
Moderate error
H
660
Moderate error
H
661
Moderate error
H
216
Description and
Error name
cause
A value other than 1 to
100 is set in CH Moving
CH Moving
average count (Frequency
average count
measurement) (RWw19,
setting error
RWw31).
(Frequency
indicates the channel
measurement)
where settings are
incorrect.
A value other than 0 to 2 is
set in CH Time unit
CH Time unit
setting (Frequency
setting error
measurement) (RWw18,
(Frequency
RWw30).
measurement)
indicates the channel
where settings are
incorrect.
A value other than 1 to
100 is set in CH Moving
CH Moving
average count (Rotation
average count
speed measurement)
setting error
(RWw19, RWw31).
(Rotation speed
indicates the channel
measurement)
where settings are
incorrect.
A value other than 0 to 2 is
set in CH Time unit
CH Time unit
setting (Rotation speed
setting error
measurement) (RWw18,
(Rotation speed
RWw30).
measurement)
indicates the channel
where settings are
incorrect.
A value other than 1 to
8000000 is set in CH
Number of pulses per
CH Number
rotation (RWw1A to
of pulses per
RWw1B, RWw32 to
rotation setting
RWw33).
error
indicates the channel
where settings are
incorrect.
A pulse from CH
Function input terminal
CH Pulse
(FUNC1 or FUNC2) is
measurement
beyond the measurable
range overflow
range (approx. 214s).
error (Function
indicates the channel
input terminal)
where settings are
incorrect.
A value other than 0 and 1
is set in CH Pulse
CH Pulse
measurement setting
measurement
(Function input terminal)
setting error
(address: 012A
(Function input
indicates the channel
terminal)
where settings are
incorrect.
Operation of when an error
occurs
Error CH
*9
*3
*9
*3
*10
*3
*10
*3
*10
*3
*11
*3
*13
, 014A
).
H
H
Action
The other
CHs
Set CH Moving average
count (Frequency
measurement) (RWw19,
RWw31) to a value between 1
and 100, and turn off then on
CH Count enable command
(RY24, RY3C).
Set CH Time unit setting
(Frequency measurement)
(RWw18, RWw30) to a value
between 0 and 2, and turn off
then on CH Count enable
command (RY24, RY3C).
Set CH Moving average
count (Rotation speed
measurement) (RWw19,
RWw31) to a value between 1
and 100, and turn off then on
CH Count enable command
(RY24, RY3C).
Set CH Time unit setting
(Rotation speed measurement)
(RWw18, RWw30) to a value
between 0 and 2, and turn off
then on CH Count enable
command (RY24, RY3C).
Set CH Number of pulses per
rotation (RWw1A to RWw1B,
RWw32 to RWw33) to a value
between 1 and 8000000, and
turn off then on CH Count
enable command (RY24,
RY3C).
Measure pulses within the
measurable range.
To resume the measurement,
take either of the following
actions.
• Input the target pulses again.
• Turn off then on CH Pulse
measurement start command
(Function input terminal)
(RY30, RY48).
Set CH Pulse measurement
setting (Function input terminal)
(address: 012A
H
or 1, and turn off then on Initial
data setting request flag (RY9).
, 014A
) to 0
H