Error code
Classification
(hexadecimal)
601
Moderate error
H
602
Moderate error
H
621
Moderate error
H
622
Moderate error
H
623
Moderate error
H
660
Moderate error
H
661
Moderate error
H
216
Description and
Error name
cause
A value other than 1 to
100 is set in CH Moving
CH Moving
average count (Frequency
average count
measurement) (RWw19,
setting error
RWw31).
(Frequency
 indicates the channel
measurement)
where settings are
incorrect.
A value other than 0 to 2 is
set in CH Time unit
CH Time unit
setting (Frequency
setting error
measurement) (RWw18,
(Frequency
RWw30).
measurement)
 indicates the channel
where settings are
incorrect.
A value other than 1 to
100 is set in CH Moving
CH Moving
average count (Rotation
average count
speed measurement)
setting error
(RWw19, RWw31).
(Rotation speed
 indicates the channel
measurement)
where settings are
incorrect.
A value other than 0 to 2 is
set in CH Time unit
CH Time unit
setting (Rotation speed
setting error
measurement) (RWw18,
(Rotation speed
RWw30).
measurement)
 indicates the channel
where settings are
incorrect.
A value other than 1 to
8000000 is set in CH
Number of pulses per
CH Number
rotation (RWw1A to
of pulses per
RWw1B, RWw32 to
rotation setting
RWw33).
error
 indicates the channel
where settings are
incorrect.
A pulse from CH
Function input terminal
CH Pulse
(FUNC1 or FUNC2) is
measurement
beyond the measurable
range overflow
range (approx. 214s).
error (Function
 indicates the channel
input terminal)
where settings are
incorrect.
A value other than 0 and 1
is set in CH Pulse
CH Pulse
measurement setting
measurement
(Function input terminal)
setting error
(address: 012A
(Function input
 indicates the channel
terminal)
where settings are
incorrect.
Operation of when an error
occurs
Error CH
*9
*3
*9
*3
*10
*3
*10
*3
*10
*3
*11
*3
*13
, 014A
).
H
H
Action
The other
CHs
Set CH Moving average
count (Frequency
measurement) (RWw19,
RWw31) to a value between 1
and 100, and turn off then on
CH Count enable command
(RY24, RY3C).
Set CH Time unit setting
(Frequency measurement)
(RWw18, RWw30) to a value
between 0 and 2, and turn off
then on CH Count enable
command (RY24, RY3C).
Set CH Moving average
count (Rotation speed
measurement) (RWw19,
RWw31) to a value between 1
and 100, and turn off then on
CH Count enable command
(RY24, RY3C).
Set CH Time unit setting
(Rotation speed measurement)
(RWw18, RWw30) to a value
between 0 and 2, and turn off
then on CH Count enable
command (RY24, RY3C).
Set CH Number of pulses per
rotation (RWw1A to RWw1B,
RWw32 to RWw33) to a value
between 1 and 8000000, and
turn off then on CH Count
enable command (RY24,
RY3C).
Measure pulses within the
measurable range.
To resume the measurement,
take either of the following
actions.
• Input the target pulses again.
• Turn off then on CH Pulse
measurement start command
(Function input terminal)
(RY30, RY48).
Set CH Pulse measurement
setting (Function input terminal)
(address: 012A
H
or 1, and turn off then on Initial
data setting request flag (RY9).
, 014A
) to 0
H