Mitsubishi NZ2GFCF-D62PD2 User Manual page 225

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

(2) Error code list (D000
When an error occurs, the ERR. LED does not turn on. The D LINK LED flashes or turns off.
Troubleshoot the problem with the CC-Link IE Field Network diagnostics. (
Error code
Error name
(hexadecimal)
Station type
D0E0
H
mismatch
Own station
D0E1
H
reserved
Station No.
D0E2
already in use
H
(own station)
Own station
D0E3
No. out of
H
range
Transient data
D217
command
H
error
Receive buffer
D2A0
H
full
Transient data
D2A3
H
length error
Station
number switch
D72A
out of range (a
H
value other
than 1 to 120)
Transient data
DF01
H
divided error
When multiple errors occur, only the latest error code is stored in CH Latest error code (RWr22, RWr3A) or CH Latest
warning code (RWr23, RWr3B).
Old errors can be checked with the error history of GX Works2.
For the error history, refer to the following.
• Checking by executing a command of the slave station (
• Error history 1 to 15 (address: 0A00
to DFFF
(D529
H
H
Description and cause
The network parameter is
incorrect or outside the range.
The network parameter is
incorrect or outside the range.
The network parameter is
incorrect or outside the range.
The network parameter is
incorrect or outside the range.
The transient data request
command is incorrect.
The target station is
overloaded and cannot
receive transient data.
The received transient data is
incorrect.
A station number out of range
has been set.
The divided transient data
have been received.
to 0AFF
H
and D52B
excluded))
H
H
Action
In the network configuration settings of the master station, change
the station type to the remote device station.
• In the network configuration settings of the master station, cancel
the reserved station setting.
• Change the station number of the module to a station number that
is not reserved.
• Set a unique station number.
• After taking the above action, turn off then on or reset all the
stations where this error has been detected.
Add the station information of the module in the network
configuration settings of the master station.
Correct the request command at the request source, and retry the
operation.
• Check the network status using the CC-Link IE Field Network
diagnostics of GX Works2.
• When the target station is overloaded and cannot receive transient
data, send the data to the target station after a while.
Correct the number of data (frame length) at the request source, and
retry the operation.
Set the station number within the allowable range.
Set the transient data size within the range that can be handled by
the module. Then send the transient data that is not divided.
Page 205, Section 11.1 (1))
) (
Page 276, Appendix 3 (14))
H
CHAPTER 11 TROUBLESHOOTING
Page 175, Section 8.21)
223