Mitsubishi NZ2GFCF-D62PD2 User Manual page 240

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

Remote input
Signal name
(RX) No.
Initial data setting
RX9
completion flag
238
• This signal is used as an interlock for turning on/off Initial data setting request flag (RY9)
when the setting values in the parameter area of the remote buffer memory are changed or
the setting values of the extended parameter area are saved into the nonvolatile memory.
• While this signal is on, the high-speed counter module does not count pulses.
This signal turns off in the following cases.
• Until Initial data setting request flag (RY9) is turned on after the module is powered on
• Initial data setting request flag (RY9) is turned off when the setting values in the parameter
area of the remote buffer memory are normal.
This signal turns on in the following case.
• When Initial data setting request flag (RY9) is turned on
Controlled by the high-speed counter module
Controlled by the program
Initial data setting completion flag
(RX9)
Initial data setting request flag
Parameter area
Remote READY
(RXB)
• After checking that the initial data setting processing is completed (this signal turns off) and
Initial data processing request flag (RX8) turns off, turn on CH Count enable command
(RY24, RY3C) to start pulse counting.
• Remote output signals other than CH Error reset command (RY36, RY4E) that are already
turned on when this signal turns off are recognized as they are turned on right after this
signal turns off.
• When Initial data processing request flag (RX8) is off and at the rising state of either of
Coincidence output 1 or Coincidence output 2 for which the preset/replace (at coincidence
output) function is enabled from the comparison result at when this signal turns off, the count
value is replaced with the preset value. (However, this operation is performed only when
Comparison output setting (address: 0100
CH Operation mode setting (address: 0120
• If an error occurs, such as when a value out of the setting range of the remote register
(RWw) or the remote buffer memory is detected, this signal does not turn off even if Initial
data setting request flag (RY9) is turned off. (This signal remains on.) In this case, remove
the error cause and turn on then off Initial data setting request flag (RY9). In addition, the
OFF time must be longer than ΔT
*1
For ΔT
, refer to Page 283, Appendix 4.
1
Description
OFF
OFF
(RY9)
The setting value is
changed by the user.
(Setting value A)
ON
The operation is
performed with
the setting value A.
) is set to Coincidence Output Function (0) and
H
, 0140
) is set to Normal Mode (0).)
H
H
*1
.
1
ON
ON
(Setting value B)
ON
OFF
The operation is
performed with
the setting value B.