Error code
Classification
(hexadecimal)
1F00
Major error
H
1F20
Moderate error
H
1F30
Moderate error
H
050
H
Minor error
*15
200
Moderate error
H
Description and
Error name
cause
The extension module is
Extension
improperly connected or
module 1
an extension module not
connection error
allowed to be connected
has been connected.
The external power supply
for the extension output
External power
module is off while the
supply OFF
external power supply
error
monitoring function is
enabled.
The parameter for
Extension
specifying the extension
module
module type has specified
parameter
a type different from the
failure
connected one.
The value in CH
Sampling count value
(RWr12 to RWr13, RWr2A
to RWr2B), CH Periodic
pulse count, difference
CH Overflow/
value (RWr12 to RWr13,
underflow error
RWr2A to RWr2B), or
(Sampling count
CH Periodic pulse count
value/Periodic
value update check
pulse count,
(RWr16 to RWr17, RWr2E
difference
to RWr2F) is outside the
value)
range of -2147483648 to
2147483647.
 indicates the channel
where settings are
incorrect.
The value in CH Present
value (RWr10 to RWr11,
RWr28 to RWr29) is
outside the range of
CH
-2147483648 to
Overflow/underf
2147483647 in the linear
low error
counter function operation.
 indicates the channel
where settings are
incorrect.
CHAPTER 11 TROUBLESHOOTING
Operation of when an error
occurs
The other
Error CH
CHs
*13
*14
*13
*2
*3
*5
*3
Action
Check the contact points on the
extension module, and if the
module is allowed to be
connected. If the same error
occurs again, a module failure
may be the cause. Please
consult your local Mitsubishi
representative.
• Check the external power
supply status for the external
output module.
• If this error occurs when the
system starts or stops,
change the timing of when
the external power supply
monitoring function is
enabled.
Correct the setting in Extension
module identification code
(address: 0200
) so that the
H
setting matches the connected
extension module and the
module points.
Adjust the values so that the
product of Input pulse speed
[pps] × Sampling/Periodic time
[s] is within the range.
Replace the present value with
the preset value.