Mitsubishi NZ2GFCF-D62PD2 User Manual page 286

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

(4) Examples of response delay time
An example is described in (a) to (d) regarding the operation of the coincidence output function in the following
condition.
• Master/local module is the QJ71GF11-T2
• Block data assurance per station is set
• Asynchronous mode
Operation of the coincidence output function
Ex.
CH
Count enable command
CH
(Coincidence output 1)
Counter value smaller
(Coincidence output 1)
Coincidence output 1
(Coincidence output 1)
Counter value greater
(Coincidence output 1)
(a) Processing time (Normal value): Master station (RY) → Remote device station (RY)
The following shows the processing time required until the high-speed counter module starts pulse input after
CH Count enable command (RY24, RY3C) is turned on.
(SM × n2) + (LS × 1) + Processing time of the high-speed counter module (ΔT
• SM: Scan time of the program in the master station
• LS: Link scan time
• n2: The value provided by rounding up the value after the decimal point of (LS ÷ SM)
284
OFF
(RY24, RY3C)
Coincidence output
enable command
OFF
(RY20, RY38)
Counter input pulse
(d)
Point setting
(RWw0 to RWw1)
(RWr0.b0)
OFF
(RX10)
Reset command
OFF
(RY10)
(RWr0.b1)
CH
Present value
(RWr10 to RWr11,
RWr28 to RWr29)
ON
ON
(a)
100
(b)
0
1
2
to
98
99
ON
(c)
ON
100
101
102
103
)
1