Mitsubishi NZ2GFCF-D62PD2 User Manual page 215

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

Error code
Classification
(hexadecimal)
Moderate error
31
H
351
Moderate error
H
359
Moderate error
H
360
Moderate error
H
366
Moderate error
H
Description and
Error name
cause
The value in Upper limit
value setting (Coincidence
output
) is smaller than
the value in Lower limit
Upper limit
value setting (Coincidence
value setting
output
).
error
 indicates the channel
(Coincidence
where settings are
output
)
incorrect.
indicates the number of
Coincidence output on
which this error occurred.
A value other than 0 to 16
is set in Cam switch
Cam switch
function, number of steps
function,
(Output 1) (address:
number of steps
1501
).
H
setting error
 indicates the channel
(Output 1)
where settings are
incorrect.
A value other than 0 to 16
is set in Cam switch
Cam switch
function, number of steps
function,
(Output 9) (address:
number of steps
1901
).
H
setting error
 indicates the channel
(Output 9)
where settings are
incorrect.
A value other than 0 to 16
is set in Cam switch
Cam switch
function, number of steps
function,
(Output 10) (address:
number of steps
1981
).
H
setting error
 indicates the channel
(Output 10)
where settings are
incorrect.
A value other than 0 to 16
is set in Cam switch
Cam switch
function, number of steps
function,
(Output 16) (address:
number of steps
1C81
).
H
setting error
 indicates the channel
(Output 16)
where settings are
incorrect.
CHAPTER 11 TROUBLESHOOTING
Operation of when an error
occurs
The other
Error CH
CHs
If the
If the
parameters are
parameters are
written with the
written with the
parameter
parameter
processing of
processing of
the slave
the slave
station, or Initial
station, or Initial
data processing
data processing
completion flag
completion flag
(RY8) or Initial
(RY8) or Initial
data setting
data setting
request flag
request flag
(RY9) is turned
(RY9) is turned
*13
*13
off then on:
off then on:
If Setting
If Setting
change request
change request
(Coincidence
(Coincidence
output
) (RY14
output
) (RY14
to RY17) is
to RY17) is
turned off then
turned off then
*6
*3
on:
on:
*7
*3
*7
*3
*7
*3
*7
*3
Action
Set the values that satisfy the
condition "Lower limit value
setting (Coincidence output
)
≤ Upper limit value setting
(Coincidence output
)", and
perform one of the following
operations.
• If Initial data processing
request flag (RX8) is on, turn
off then on Initial data
processing completion flag
(RY8).
• If the parameters are written
with the parameter
processing of the slave
station, or Initial data setting
completion flag (RX9) is on,
turn off then on Initial data
setting request flag (RY9).
• If Initial data processing
request flag (RX8) and Initial
data setting completion flag
(RX9) are off, turn off then on
Setting change request
(Coincidence output
)
(RY14 to RY17).
Set Cam switch function,
number of steps (Output 1)
(address: 1501
) to a value
H
between 0 and 16, and turn off
then on CH Cam switch
execute command (RY26,
RY3E).
Set Cam switch function,
number of steps (Output 9)
(address: 1901
) to a value
H
between 0 and 16, and turn off
then on CH Cam switch
execute command (RY26,
RY3E).
Set Cam switch function,
number of steps (Output 10)
(address: 1981
) to a value
H
between 0 and 16, and turn off
then on CH Cam switch
execute command (RY26,
RY3E).
Set Cam switch function,
number of steps (Output 16)
(address: 1C81
) to a value
H
between 0 and 16, and turn off
then on CH Cam switch
execute command (RY26,
RY3E).
213